SensoIRIS MCP150MR
Brendi: TELETEK
Kodi: SensoIRIS MCP150MR
Description
The addressable manual call point SensoIRIS MCP150MR is
Designed for application in addressable fire alarm systems, which support TTE communication protocol.
The call point has a built-in isolator module which when used allows continuous
Working element (2 parts):
Frangible element – non-resettable (a break glass);
Operating element – resettable (a button);
Call point type (method of operation according EN 54-11) – B;
Built-in isolator module;
EN54-11 and EN54-17 certified.
Operating voltage | 15÷32VDC |
Current consumption without communication (max) | 125µА@27VDC |
Current consumption with communication (max) | 160µА@27VDC |
Current consumption in Fire mode | 3mA |
Wiring cables | 0.5mm² ÷2.5mm² |
Working temperature | -10°C ÷ +60°C |
Material, color | metal powder-coated, red |
Indication “Fire alarm” | red LED |
Dimensions | 125x125x36mm |