IVY Extinguishing

IVY Extinguishing


Kodi: IVY Extinguishing

Description

IVY is an extinguishing conventional fire control panel.

The panel is designed for using together with systems for gas, powder, aerosol, water and other types of active extinguishing.

Inputs Specifications:

2 Conventional Zones for extinguishing

1 Conventional Zone for Fire Alarm

Low Pressure input – supervised balanced input

Manual release input – supervised balanced input

Mode select input – supervised balanced input for switching between Manual and Automatic operation mode

Hold input – supervised balanced input

Enable/Disable – supervised balanced input

Flow Control – supervised balanced input

 

Outputs Specifications:

SND 1 (Sounder 1) – Monitored, 24VDC, 300mA

SND 2 (Sounder 2) – Monitored, 24VDC, 300mA

Stage 1 relay “Fire Alarm” (NC, COM, NO), 5-30VDC/1A

Stage 2 relay “Extinguishing Activated” (NC, COM, NO), 5-30VDC/1A

Fault relay(NC, COM, NO), 5-30VDC/1A

Extinguish output (EN 12094-1), Monitored, 24VDC/1A 5min, 24VDC/3A 20ms

OC1 – in case of Hold Activation – open collector type

OC2 – in case of extinguish disable – open collector type

OC3 – in case of low pressure – open collector type

OC4 – in case of manual mode active – open collector type

Main Power Supply110-230VAC ±10%
Frequency47-60Hz
Back-up Power Supply2 x 12V/ 7Ah
Electrical output26VDC; 1.5A
Internal resistance of the battery Ri< 0.3Ω
Consumption0.3A@230VAC; 0.7@110VAC
Operating temperature-5°C to +40°C
Relative humidity resistance(93 ± 3)% @ 40°C
Dimensions of the metal box324x314x82mm