IVY Extinguishing
Description
IVY is an extinguishing conventional fire control panel.
The panel is designed for using together with systems for gas, powder, aerosol, water and other types of active extinguishing.
Inputs Specifications:
2 Conventional Zones for extinguishing
1 Conventional Zone for Fire Alarm
Low Pressure input – supervised balanced input
Manual release input – supervised balanced input
Mode select input – supervised balanced input for switching between Manual and Automatic operation mode
Hold input – supervised balanced input
Enable/Disable – supervised balanced input
Flow Control – supervised balanced input
Outputs Specifications:
SND 1 (Sounder 1) – Monitored, 24VDC, 300mA
SND 2 (Sounder 2) – Monitored, 24VDC, 300mA
Stage 1 relay “Fire Alarm” (NC, COM, NO), 5-30VDC/1A
Stage 2 relay “Extinguishing Activated” (NC, COM, NO), 5-30VDC/1A
Fault relay(NC, COM, NO), 5-30VDC/1A
Extinguish output (EN 12094-1), Monitored, 24VDC/1A 5min, 24VDC/3A 20ms
OC1 – in case of Hold Activation – open collector type
OC2 – in case of extinguish disable – open collector type
OC3 – in case of low pressure – open collector type
OC4 – in case of manual mode active – open collector type
Main Power Supply | 110-230VAC ±10% |
Frequency | 47-60Hz |
Back-up Power Supply | 2 x 12V/ 7Ah |
Electrical output | 26VDC; 1.5A |
Internal resistance of the battery Ri | < 0.3Ω |
Consumption | 0.3A@230VAC; 0.7@110VAC |
Operating temperature | -5°C to +40°C |
Relative humidity resistance | (93 ± 3)% @ 40°C |
Dimensions of the metal box | 324x314x82mm |